The CBT/1 and CBT-H bar-type current transformers are designed
for use in metering 600 volt circuits.
- 10 kV BIL
- 25 through 60 Hertz
- Primary Amperes 100-800
- Non-removable primary bar can be rotated
The ring-type core and fully distributed winding are assembled to a
glass-filled polypropylene window liner. This assembly and an aluminum
base support are injection molded in thermoplastic rubber.
Thermoplastic rubber insulating material is permanently molded to
the core and coil assembly, resulting in a compact unit with excellent
mechanical, thermal, and dielectric characteristics.
The primary copper bar is electro-tin plated and can be rotated for
convenient positioning of the transformer. It is equipped with a
potential terminal suitable for #6 to #14 wire.
Compression-type secondary terminals will accommodate #14
through #2 wire. Each unit is equipped with a retainable shorting
device and clear plastic cover, suitable for locking with a meter seal. |